Batteries |
|
|
|
Our Tubular Ultra Low Maintenance Battery is made using the special
technology by which the active material is encapsulated in polyester
tubes to prevent 'Shedding'. The electrode geometry facilities 'cyclic'
deep discharges i.e. long repetitive power outages. They are
recommended for back up power for UPS & Inverters where
environmental conditions are tough and high ambient temperatures are
common. Tubat Tobular proved to be most reliable source of back up
power for Inverters and UPS operating under demanding conditions. These
are capable of long hours of backup.
Applications - Stored Power For
- UPS [Un-Interrupted Power Supply
- Communication Equipments
- Solar Power Systems
- Lighting
- Domestic
- Industrial
- Inverter
- Wind Mills
- And Other Stationery Applications
Salient Features
- Steady Output
- Aquatrap Ventplug Ensures
- Low Maintenance
- No Acid Fumes
- Eco Friendly
- Low Antimony Allow
- Large Top-Of-Plate Acid Head Room
- Quick Recovery From Deep Discharge
- Extra Backup Time
Technical Specifications
Tubular Regular Series
| Sl no. |
Voltage (C10) |
Size - mm (LxWxH) ± 5mm |
| 1 |
12V 120 AH |
440x185x415 |
| 2 |
12V 150 AH |
440x185x415 |
| 3 |
12V 180 AH |
440x185x415 |
| 4 |
12V 200 AH |
440x185x415 |
| 5 |
12V 220 AH |
440x185x415 |
| 6 |
12V 240 AH |
440x185x415 |
A) Initial Charging Instructions
Filling Gravity: 1.230 0.005 @ 27°C
Rest Period : 12
hours
Charging Current: 0.10C Amps
Charging Duration: 48 hours (MINIMUM)
Final Gravity : 1.240 ~1.250 @ 27°C
B) Normal Charging Instructions
(After a capacity discharge) Normal charging rate: 0.1 OC Amps Condition for fully charged state: (For both a & b)
Charge till constancy in voltage and specify gravity reading for 3 consecutive hours and free gassing in all the cells
C) Maintenance Instructions
Recharge battery after prolonged use. Keep battery top and terminal clean & dry Ensure good ventilation in the room
Toping with distilled water 2 to 3 times a year Wooden or plastic (No
conductivity) planks should be used for placing the battery
|
|
|
| |
|
| |
|